Submerged Arc Furnace Transformer
Overview
Continuous smelting duty requires the output voltage steps and current schedule to be matched to the furnace. The source catalogue distinguishes on-load and off-circuit regulation. A furnace transformer supplies electrical power to an industrial furnace according to its process requirements. The reference catalogue covers submerged arc, steelmaking arc, ladle refining, electroslag and power-frequency furnace applications. These duties should be treated separately because their operating cycles, secondary voltages and regulation requirements differ. The selection process starts with the furnace type, rated power and required output range. Input voltage, phase arrangement, impedance requirements and cooling conditions are then reviewed with the furnace equipment supplier. Available catalogue tables provide reference configurations for each family, including ratings, dimensions and weights where stated. A listed configuration is not a promise that it fits every furnace with the same nominal capacity. For a new furnace or replacement project, send the electrical specification, operating cycle and connection requirements. The technical proposal will define the selected transformer arrangement and accessories. Installation dimensions and lifting requirements should be confirmed against the approved project drawing before site work begins.
Features and Benefits
- Furnace-specific selection matches the electrical process.
- Dedicated reference tables allow comparison of relevant configurations.
Technical Specifications
| Model number |
Rated capacity (kVA) |
Rated voltage | Connection symbol |
Product weight (kg) |
Track gauge (mm) |
Overall dimensions (L × W × H), mm | |||
|---|---|---|---|---|---|---|---|---|---|
|
Primary voltage (kV) |
Secondary (V) |
Body weight | Oil weight | Gross weight | |||||
| HKSSP-880/10 | 800 | 10 | 120-105-85-70 4 | Yd11 | 2700 | 1880 | 5950 | 1070×1070 | 2500×1500×2500 |
| HKSSP-1000/10 | 1000 | 10 | 80-60 7 steps | Yd11 | 2830 | 1650 | 5950 | 1070×1070 | 1600×1300×2500 |
| HKSSP-1250/10 | 1250 | 10 | 90-60-50 5 steps | Yd11 | 4100 | 2850 | 9800 | 1070×1070 | 3200×1700×2500 |
| HKS-1250/10 | 1250 | 10 | 130-105 6 steps | Yd11 | 3330 | 1940 | 7000 | 1070×1070 | 2900×2250×2160 |
| HKSSP-1500/35 | 1500 | 35 | 240-210-135 12 steps | Yd11 | 4350 | 3900 | 12600 | 1435×1435 | 3900×1800×2800 |
| HKS-1650/10 | 1650 | 10 | 140-100 6 steps | Yd11 | 4240 | 2470 | 8900 | 1070×1070 | 2940×1950×2300 |
| HSKZ-1800/10 | 1800 | 10 | 160-141-126 9 steps | Yd11 | 4290 | 2500 | 9000 | 1435×1435 | 2800×1800×3250 |
| HKSSP-2000/35 | 2000 | 35 | 240-150 9 steps | Yd11 | 5200 | 3600 | 12400 | 1435×1435 | 3600×1700×2700 |
| HKSSP-2500/6 | 2500 | 6 | 104-80 11 steps | Yd11 | 6100 | 3800 | 14200 | 1070×1070 | 4000×2100×2800 |
| HTSSP-2500/10 | 2500 | 10 | 98.5-95-83 5 steps | Yd11 | 6190 | 3610 | 13000 | 1435×1435 | 2810×1880×3360 |
| HTSSP-2500/35 | 2500 | 35 | 88-76-70 5 steps | Dd0 | 6670 | 3890 | 14000 | 1435×1435 | 3780×1950×3450 |
| HKSZ-3000/10 | 3000 | 10 | 410-350-190 23 steps | Yd11 | 7430 | 4330 | 15600 | 1435×1435 | 4020×2650×4000 |
| HTSSP-3200/10 | 3200 | 10 | 220-110 13 steps | Yd11 | 6900 | 4030 | 14500 | 1435×1435 | 4050×2550×2900 |
| HKSSP-3200/35 | 3200 | 35 | 250-150 21 steps | Yd11 | 6800 | 4750 | 16000 | 1435×1435 | 4100×2300×4000 |
| HKSSP-3500/35 | 3500 | 35 | 114-92-84 5 steps | Yd11 | 7140 | 4170 | 15000 | 1435×1435 | 3800×2050×3250 |
| HTSSP-3500/35 | 3500 | 35 | 112-102-84 5 steps | Yd11 | 7480 | 4360 | 15700 | 1435×1435 | 3750×2150×3350 |
| HKSSP-3500/35 | 3500 | 35 | 230-160 15 steps | Yd11 | 8800 | 6250 | 19500 | 1435×1435 | 4100×3000×3800 |
| HKSSP-3500/35 | 3500 | 35 | 250-210-170 9 steps | Yd11 | 7428 | 4500 | 15800 | 1435×1435 | 4000×2050×4000 |
| HKSSP-4000/10 | 4000 | 10 | 120-96-80 7 steps | Yd11 | 6810 | 3970 | 14300 | 1435×1435 | 3680×1900×3000 |
| HKSSP-4000/10 | 4000 | 10 | 123-105-93 6 steps | Yd11 | 7330 | 4280 | 15400 | 1435×1435 | 3850×2250×3000 |
| HKSSP-4500/35 | 4500 | 35 | 120-105-90 7 steps | Yd11 | 8100 | 4720 | 17000 | 1435×1435 | 4100×1950×3350 |
| HKSSP-4500/10 | 4500 | 10 | 126-109-96 5 steps | Yd11 | 8570 | 5000 | 18000 | 1435×1435 | 4050×2250×3350 |
| HCSSP-5000/10 | 5000 | 10 | 124-71 8 steps | Yd11 | 10000 | 5830 | 21000 | 1435×1435 | 4100×2280×3300 |
| HKSSPZ-5000/10 | 5000 | 10 | 200-176-120 11 steps | Yd11 | 9200 | 5100 | 17200 | 1435×1435 | 4000×2300×4200 |
| HKSSP-5000/35 | 5000 | 35 | 132-95 7 steps | Dd0 | 10950 | 6390 | 23000 | 1435×1435 | 4280×2700×4000 |
| HKSSPZ-5000/35 | 5000 | 35 | 197-109-60 19 steps | Yd11 | 12380 | 7220 | 26000 | 2000×2000 | 4450×2850×4120 |
| HKSSP-6300/10 | 6300 | 10 | 190-135-110 5 steps | Yd11 | 9500 | 4500 | 18200 | 1435×1435 | 3800×2300×4100 |
| HKSSPZ-6300/20 | 6300 | 20 | 138-120-104 18 steps | Yd11 | 11500 | 4850 | 18520 | 1435×1435 | 4000×2100×4100 |
| HTSSP-6300/35 | 6300 | 35 | 130-118-94 7 steps | Dd0 | 10950 | 6390 | 23000 | 1435×1435 | 4170×2640×3600 |
| HKSSP-6300/35 | 6300 | 35 | 125-119-85 7 steps | Dd0 | 12380 | 7220 | 26000 | 1435×1435 | 4890×2410×3600 |
| HTSSPZ-6300/35 | 6300 | 35 | 135-119-104 7 steps | Yd11 | 12860 | 7500 | 27000 | 1435×1435 | 4455×2850×3980 |
| HCSSP-6300/35 | 6300 | 35 | 133-100 11 steps | Dd0 | 10520 | 5830 | 21000 | 1435×1435 | 4750×2350×3870 |
| HKSSPZ-7000/20 | 7000 | 20 | 150-126-102 17 steps | Yd11 | 11000 | 7500 | 22500 | 1435×1435 | 4100×2400×4200 |
| HKSSP-7000/35 | 7000 | 35 | 136-120-104 7 steps | Dd0 | 10000 | 5830 | 21000 | 1435×1435 | 4885×2300×3800 |
| HTSSP-7000/35 | 7000 | 35 | 132-112-100 9 steps | Dd0 | 10300 | 6000 | 21500 | 1435×1435 | 4650×2400×3780 |
| HCSSP-7000/35 | 7000 | 35 | 135-112-104 9 steps | Dd0 | 10240 | 5970 | 21500 | 1435×1435 | 4700×2300×3800 |
| HTSSP-7500/35 | 7500 | 35 | 135-125-104 8 steps | Dd0 | 9520 | 5560 | 20000 | 1435×1435 | 4300×2200×3850 |
| HKSFPZ-7500/35 | 7500 | 35 | 148-133-188 9 steps | Dd0 | 15710 | 9170 | 33000 | 1435×1435 | 4350×2400×3780 |
| HCSFPZ-8000/35 | 8000 | 35 | 136-120-108 13 steps | Yd11 | 12800 | 6960 | 25600 | 1435×1435 | 4200×2600×3800 |
| HCSFPZ-8000/35 | 8000 | 35 | 143-126-108 15 steps | Yd11 | 13800 | 7500 | 27600 | 1435×1435 | 5140×2800×4040 |
| HCSSPZ-8000/35 | 8000 | 35 | 136-120-108 7 steps | Dd0 | 11900 | 6940 | 25000 | 1435×1435 | 4200×2650×3800 |
| HTSFP-8000/35 | 8000 | 35 | 147-126-110 8 steps | Dd0 | 12380 | 7220 | 26000 | 1435×1435 | 3750×2800×3980 |
| HKSSPZ-8000/66 | 8000 | 66 | 145-124-115 9 steps | Yd11 | 18100 | 10560 | 38000 | 1435×1435 | 4500×3300×5200 |
| HTSSPZ-9000/35 | 9000 | 35 | 158-128-110 13 steps | Yd11 | 13810 | 8060 | 29000 | 1435×1435 | 4300×2050×4300 |
| HCSFPZ-10000/35 | 10000 | 35 | 156-131-105 17 steps | Yd11 | 18500 | 10050 | 37000 | 1435×1435 | 3800×2800×4400 |
| HCSFPZ-10000/35 | 10000 | 35 | 157-131-118 13 steps | Yd11 | 16600 | 9020 | 33200 | 1435×1435 | 4440×2800×3890 |
| HCSFPZ-10000/35 | 10000 | 35 | 160-148-120 15 steps | Yd11 | 16250 | 8830 | 32500 | 1435×1435 | 4200×2800×3800 |
| HKSSPZ-10000/35 | 10000 | 35 | 171-132-123 9 steps | Dd0 | 14050 | 8190 | 29500 | 1435×1435 | 3800×2800×4650 |
| HCSSPZ-10000/35 | 10000 | 35 | 160-130-115 17 steps | Dd0 | 14760 | 8610 | 31000 | 1435×1435 | 3900×2800×4800 |
| HCSSPZ-12000/35 | 12000 | 35 | 152-126-114 17 steps | Yd11 | 19750 | 10730 | 39500 | 1435×1435 | 4270×2823×4535 |
| HCSFPZ-12500/35 | 12500 | 35 | 160-145-124 15 steps | Yd11 | 19700 | 10710 | 39400 | 1435×1435 | 3840×2800×4170 |
| HCSFPZ-12500/35 | 12500 | 35 | 175-153-134 13 steps | Yd11 | 17800 | 9670 | 35600 | 1435×1435 | 4000×2800×4000 |
| HKSSPZ-12500/35 | 12500 | 35 | 190-110 17 steps | Yd11 | 23000 | 12500 | 46000 | 1435×1435 | 4200×2800×4500 |
| HKSSP-12500/35 | 12500 | 35 | 365-265-153 9 steps | Yd11 | 15700 | 9200 | 33000 | 1435×1435 | 4500×2800×4580 |
| HTSSP-12500/35 | 12500 | 35 | 166-140-126 9 steps | Yd11 | 15710 | 9170 | 33000 | 1435×1435 | 3800×2400×4600 |
| HCSSP-12500/35 | 12500 | 35 | 175-153-134 9 steps | Yd11 | 15240 | 8890 | 32000 | 1435×1435 | 3980×2870×3900 |
| HKSSP-12500/35 | 12500 | 35 | 400-300-200 17 steps | Yd11 | 23000 | 11200 | 42500 | 1435×1435 | 4300×3400×4500 |
| HTSSPZ-14000/35 | 14000 | 35 | 180-135-120 13 steps | Yd11 | 17140 | 10000 | 36000 | 1435×1435 | 3900×2950×4680 |
| HCSSPZ-14500/35 | 14500 | 35 | 185-167-137 13 steps | Yd11 | 17620 | 10280 | 37000 | 1435×1435 | 4900×2800×4750 |
| HKSSPZ-15000/35 | 15000 | 35 | 176-152-122 19 steps | Yd11 | 25400 | 14000 | 52000 | 1435×1435 | 4500×3200×4600 |
| HKSSP-15000/35 | 15000 | 35 | 370-313-295 13 steps | Yd11 | 15710 | 9170 | 33000 | 1435×1435 | 4600×2850×4100 |
| HTSSP-15000/35 | 15000 | 35 | 167-151-127 9 steps | Dd0 | 16670 | 9720 | 35000 | 1435×1435 | 3800×2900×4650 |
| HCSSP-16500/35 | 16500 | 35 | 170-149 7 steps | Dd0 | 19050 | 11110 | 40000 | 1435×1435 | 5250×2900×4500 |
| HTSSPZ-16500/35 | 16500 | 35 | 178-154-136 8 steps | Dd0 | 18570 | 10830 | 39000 | 1435×1435 | 3635×3180×4700 |
| HKSSP-16500/35 | 16500 | 35 | 300-250-195 19 steps | Yd11 | 24200 | 12500 | 44000 | 1435×1435 | 4300×3450×4560 |
| HKSSP-16500/35 | 16500 | 35 | 420-336-261 13 steps | Yd11 | 18100 | 10560 | 38000 | 1435×1435 | 4860×2830×4650 |
| HKSSP-18000/35 | 18000 | 35 | 430-360-260 13 steps | Yd11 | 18330 | 10690 | 38500 | 1435×1435 | 5150×2850×4430 |
| HCSSPZ-18000/35 | 18000 | 35 | 180-158-135 13 steps | Dd0 | 22380 | 13060 | 47000 | 1435×1435 | 4300×3890×4750 |
| HKSSP-20000/35 | 20000 | 35 | 410-325-237 27 steps | Dd0 | 20950 | 12220 | 44000 | 1435×1435 | 5100×2800×4750 |
| HCSFPZ-20000/35 | 20000 | 35 | 185-171-134 9 steps | Dd0 | 20480 | 11940 | 43000 | 1435×1435 | 4050×3560×4560 |
| HKSSP-23000/35 | 23000 | 35 | 445-360-265 27 steps | Dd0 | 22860 | 13330 | 48000 | 1435×1435 | 5350×2850×4700 |
| HCSFPZ-25000/35 | 25000 | 35 | 224-187-148 13 steps | Yd11 | 28570 | 16670 | 60000 | 1435×1435 | 5000×3920×4700 |
| HTSSPZ-25000/35 | 25000 | 35 | 240-180-140 35 steps | Yd11 | 39000 | 21000 | 76000 | 2000×2000 | 4800×3800×5400 |
| HKSFPZ-25000/35 | 25000 | 35 | 480-375-190 35 steps | Yd11 | 31430 | 18330 | 66000 | 1435×1435 | 6050×3800×4550 |
| HCSFPZ-27500/35 | 27500 | 35 | 239-189-144 13 steps | Yd11 | 32860 | 19170 | 69000 | 1435×1435 | 4350×3800×4500 |
| HKDSPZ-3000/10 | 3000 | 10 | 110-50 15 steps | Ii0 | 6500 | 3800 | 13500 | 1435×1435 | 3200×2400×2900 |
| HCDSPZ-4200/35 | 4200 | 35 | 170-152-122 7 steps | Ii0 | 8420 | 4320 | 16000 | 1435×1435 | 2655×2700×2930 |
| HTDSPZ-5500/35 | 5500 | 35 | 169-136-121 9 steps | Ii0 | 9520 | 5560 | 20000 | 1435×1435 | 3400×2950×3900 |
| HCDFPZ-5500/35 | 5500 | 35 | 185-164-117 9 steps | Ii0 | 14740 | 7570 | 28000 | 1435×1435 | 3100×3300×4560 |
| HKDSPZ-5500/35 | 5500 | 35 | 350-280-200 19 steps | Ii0 | 8200 | 4800 | 17600 | 1435×1435 | 3400×2400×4200 |
| HKDSPZ-5500/35 | 5500 | 35 | 400-340-300 19 steps | Ii0 | 11000 | 9100 | 27000 | 1435×1435 | 3100×2800×4100 |
| HCDSPZ-8500/35 | 8500 | 35 | 240-186-113 10 steps | Ii0 | 17900 | 9200 | 34000 | 1435×1435 | 3550×2980×4200 |
| HCDFPZ-8500/35 | 8500 | 35 | 243-183-146 8 steps | Ii0 | 16320 | 8380 | 31000 | 1435×1435 | 4185×3000×4410 |
| HCDSPZ-8500/35 | 8500 | 35 | 220-178-129 13 steps | Ii0 | 14740 | 7570 | 28000 | 1435×1435 | 4400×3210×4410 |
| HKDSPZ-8500/110 | 8500 | 110 | 440-362-286 19 steps | Ii0 | 17600 | 10900 | 37000 | 1435×1435 | 4100×3300×4800 |
| HCDSPZ-9000/35 | 9000 | 35 | 205-169-121 9 steps | Ii0 | 16320 | 8380 | 31000 | 1435×1435 | 4100×3015×4450 |
| HCDSPZ-9000/35 | 9000 | 35 | 205-169-161 19 steps | Ii0 | 16750 | 9100 | 33500 | 1435×1435 | 3500×3100×4450 |
| HCDSPZ-9000/35 | 9000 | 35 | 234-185-136 27 steps | Ii0 | 15900 | 8640 | 31800 | 1435×1435 | 4300×3200×4800 |
| HKDSPZ-10000/35 | 10000 | 35 | 500-420-300 35 steps | Ii0 | 17600 | 10000 | 34000 | 1435×1435 | 3400×3000×4400 |
| HCDSPZ-10000/35 | 10000 | 35 | 244-178-120 17 steps | Ii0 | 16840 | 8650 | 32000 | 1435×1435 | 3540×3100×4800 |
| HCDSPZ-10000/35 | 10000 | 35 | 240-198-140 17 steps | Ii0 | 15790 | 8110 | 30000 | 1435×1435 | 3600×3210×4950 |
| HKDSPZ-10500/35 | 10500 | 35 | 240-198-138 35 steps | Ii0 | 18000 | 9600 | 30500 | 1435×1435 | 3420×2900×4200 |
| HCDSPZ-11000/35 | 11000 | 35 | 248-220-157 13 steps | Ii0 | 16840 | 8650 | 32000 | 1435×1435 | 4200×3250×4100 |
| HTDSPZ-12000/35 | 12000 | 35 | 850-550-250 25 steps | Ii0 | 26000 | 10500 | 44000 | 1435×1435 | 3900×3100×4300 |
| HTDSPZ-13500/35 | 13500 | 35 | 260-220-109 35 steps | Ii0 | 22000 | 10500 | 38000 | 1435×1435 | 3300×3300×4400 |
* Values are reference data; project guarantees are confirmed in the technical agreement.
Packing & Delivering
Multi-layer protection and expert logistics for safe global transit.
FAQ's
Q: What Determines The Correct Model?
A: The process duty and electrical specification, rather than the product name alone.
Q: Are All Catalogue Values Guaranteed For A New Project?
A: The selected configuration and guaranteed values must be agreed in the technical specification.
Q: What Should I Send For A Quotation? (Electric Arc Furnace Transformer) (Submerged Arc Furnace Transformer)
A: Furnace type; capacity; input/output voltage; duty cycle; tap control; cooling.