Oil-Immersed Distribution Transformer
Overview
An oil-immersed distribution transformer supplies the required voltage for a distribution network or connected facility. The available reference documents include 10 kV-class three-phase, two-winding configurations with off-circuit or on-load voltage regulation. Selection is based on the incoming network, required secondary supply and expected load. Capacity, frequency, vector group, impedance and tap range should be specified together. Tank construction, cooling and accessories are then matched to the installation. The source materials describe sealed tank and corrugated cooling arrangements, but the final configuration depends on the selected model. For quotations, provide the electrical specification and installation environment, including any dimensional restrictions. Losses and efficiency should be evaluated using the values and test conditions for the actual model. General percentage savings without a defined comparison are not a substitute for guaranteed performance data. The final proposal will identify the agreed ratings, accessories, tests and delivery configuration for the project.
Features and Benefits
- Model-specific loss data supports meaningful comparison.
- Tank and accessories are selected for the installation.
Technical Specifications
10kV oil-immersed three-phase double-winding off-circuit tap changing distribution transformer energy efficiency class
|
Rated capacity (kVA) |
Rated voltage and tapping range | Vector group |
No load current (%) |
Impedance voltage (%) |
No load losses (W) |
On load losses (W) |
|||
|---|---|---|---|---|---|---|---|---|---|
| HV |
Tapping range (%) |
LV | Dyn11/Yzn11 | Yyn0 | |||||
| 30 | 6 | ±2×2.5 | 0.4 | Dyn11 | 1.20 | 4.0 | 65 | 455 | 430 |
| 50 | 6 | ±2×2.5 | 0.4 | Dyn11 | 1.04 | 4.0 | 80 | 655 | 625 |
| 63 | 6 | ±2×2.5 | 0.4 | Dyn11 | 0.96 | 4.0 | 90 | 785 | 745 |
| 80 | 6 | ±2×2.5 | 0.4 | Dyn11 | 0.96 | 4.0 | 105 | 945 | 900 |
| 100 | 6 | ±2×2.5 | 0.4 | Dyn11 | 0.88 | 4.0 | 120 | 1140 | 1080 |
| 125 | 6 | ±2×2.5 | 0.4 | Dyn11 | 0.88 | 4.0 | 135 | 1360 | 1295 |
| 160 | 6 | ±2×2.5 | 0.4 | Dyn11 | 0.80 | 4.0 | 160 | 1665 | 1585 |
| 200 | 6 | ±2×2.5 | 0.4 | Dyn11 | 0.80 | 4.0 | 190 | 1970 | 1870 |
| 250 | 6 | ±2×2.5 | 0.4 | Dyn11 | 0.72 | 4.0 | 230 | 2300 | 2195 |
| 315 | 6.3 | ±2×2.5 | 0.4 | Yzn11 | 0.72 | 4.0 | 270 | 2760 | 2630 |
| 400 | 10 | ±5 | 0.4 | Yyn0 | 0.64 | 4.0 | 330 | 3250 | 3095 |
| 500 | 10.5 | ±5 | 0.4 | Yyn0 | 0.64 | 4.0 | 385 | 3900 | 3710 |
| 630 | 10.5 | ±5 | 0.4 | Yyn0 | 0.48 | 4.5 | 460 | 4460 | |
| 800 | 10.5 | ±5 | 0.4 | Yyn0 | 0.48 | 4.5 | 560 | 5400 | |
| 1000 | 10.5 | ±5 | 0.4 | Yyn0 | 0.48 | 4.5 | 665 | 7415 | |
| 1250 | 10.5 | ±5 | 0.4 | Yyn0 | 0.40 | 4.5 | 780 | 8640 | |
| 1600 | 10.5 | ±5 | 0.4 | Yyn0 | 0.40 | 4.5 | 940 | 10440 | |
| 2000 | 10.5 | ±5 | 0.4 | Yyn0 | 0.32 | 5.0 | 1085 | 13180 | |
| 2500 | 10.5 | ±5 | 0.4 | Yyn0 | 0.32 | 5.0 | 1280 | 15270 | |
* Values are reference data; project guarantees are confirmed in the technical agreement.
10kV oil-immersed three-phase double-winding on-load regulating distribution transformer
|
Rated capacity (kVA) |
Rated voltage and tapping range | Vector group |
No load current (%) |
Impedance voltage (%) |
No load losses (W) |
On load losses (W) |
||
|---|---|---|---|---|---|---|---|---|
| HV |
Tapping range (%) |
LV | ||||||
| 200 | 6 | ±4×2.5 | 0.4 | Dyn11 | 0.80 | 4.0 | 0.31 | 2.90 |
| 250 | 6 | ±4×2.5 | 0.4 | Dyn11 | 0.72 | 4.0 | 0.35 | 3.42 |
| 315 | 6 | ±4×2.5 | 0.4 | Dyn11 | 0.72 | 4.0 | 0.43 | 4.10 |
| 400 | 6 | ±4×2.5 | 0.4 | Dyn11 | 0.64 | 4.0 | 0.51 | 4.95 |
| 500 | 6 | ±4×2.5 | 0.4 | Dyn11 | 0.64 | 4.0 | 0.61 | 5.89 |
| 630 | 6.3 | ±4×2.5 | 0.4 | Dyn11 | 0.48 | 4.0 | 0.77 | 7.26 |
| 800 | 10 | ±4×2.5 | 0.4 | Yyn0 | 0.48 | 4.5 | 0.90 | 8.89 |
| 1000 | 10.5 | ±4×2.5 | 0.4 | Yyn0 | 0.48 | 4.5 | 1.09 | 10.4 |
| 1250 | 10.5 | ±4×2.5 | 0.4 | Yyn0 | 0.40 | 4.5 | 1.25 | 12.3 |
| 1600 | 10.5 | ±4×2.5 | 0.4 | Yyn0 | 0.40 | 4.5 | 1.54 | 14.7 |
| 2000 | 10.5 | ±4×2.5 | 0.4 | Yyn0 | 0.32 | 5.0 | 1.82 | 18.6 |
| 2500 | 10.5 | ±4×2.5 | 0.4 | Yyn0 | 0.32 | 5.0 | 2.14 | 21.6 |
* Values are reference data; project guarantees are confirmed in the technical agreement.
Packing & Delivering
Multi-layer protection and expert logistics for safe global transit.
FAQ's
Q: How Are Price And Lead Time Confirmed?
A: They are confirmed after reviewing the specification and quantity.
Q: What Information Is Needed For A Quotation? (Oil-Immersed Distribution Transformer)
A: Capacity; primary/secondary voltage; frequency; loss requirements; taps; site.
Q: Can I Use A Generic Efficiency Figure?
A: Use the value and loading condition for the selected model.