110 kV Oil-Immersed Power Transformer
Overview
A 110 kV oil-immersed power transformer is selected for power conversion at the specified system voltage level. The reference catalogue provides configurations with rated capacity, winding voltages, tapping ranges, vector groups and impedance values. On-load and off-circuit tap-changing arrangements are listed separately and must be selected to suit the operating requirement. The design review should establish the required number of windings, network voltages, load profile and installation environment. Rated voltage alone is not enough to define a complete transformer specification. Buyers should also provide the frequency, required losses, insulation requirements, cooling arrangement and applicable project specification. Accessories, terminal arrangements and protection interfaces are agreed with the installation designer. For replacement projects, include the existing nameplate and foundation drawing. The catalogue tables supplied with this material package are reference data from the existing product documents. Final guaranteed values, test scope and overall dimensions must be confirmed in the project technical agreement and approved drawing before manufacture.
Features and Benefits
- Separate tap-changing configurations support different operating requirements.
- Project-specific electrical and mechanical review supports installation coordination.
Technical Specifications
110kV oil-immersed three-phase double-winding off-circuit tap changing power transformer
|
Rated capacity (kVA) |
Rated voltage and tapping range | Vector group |
No load current (%) |
Impedance voltage (%) |
No load losses (kW) |
On load losses (kW) |
||
|---|---|---|---|---|---|---|---|---|
| HV |
Tapping range (%) |
LV | ||||||
| 6300 |
110 115 121 |
±2×2.5 |
6.3 6.6 10.5 |
YNd11 | 0.5 | 10.5 | 4.1 | 32 |
| 8000 | 0.5 | 4.9 | 38 | |||||
| 10000 | 0.46 | 5.8 | 45 | |||||
| 12500 | 0.46 | 6.8 | 53 | |||||
| 16000 | 0.43 | 8.3 | 65.7 | |||||
| 20000 | 0.43 | 9.7 | 79 | |||||
| 25000 | 0.4 | 11.4 | 94 | |||||
| 31500 | 0.36 | 13.5 | 111 | |||||
| 40000 | 0.36 | 16.2 | 133 | |||||
| 50000 | 0.34 | 19.4 | 158 | |||||
| 63000 | 0.3 | 22.9 | 187 | |||||
| 75000 |
13.8 15.75 18 21 |
0.26 | 12-14 | 26.0 | 212 | |||
| 90000 | 0.24 | 29.9 | 245 | |||||
| 120000 | 0.22 | 37.3 | 303 | |||||
| 150000 | 0.19 | 44.1 | 359 | |||||
| 180000 | 0.16 | 49.5 | 411 | |||||
* Values are reference data; project guarantees are confirmed in the technical agreement.
110kV oil-immersed three-phase three-winding off-circuit tap changing transformer
|
Rated capacity (kVA) |
Rated voltage and tapping range | Vector group |
No load current (%) |
Short-circuit impedance (%) |
No load losses (kW) |
On load losses (kW) |
||||
|---|---|---|---|---|---|---|---|---|---|---|
| HV |
Tapping range (%) |
MV | LV | Step-up | Step-down | |||||
| 6300 |
110 115 121 |
±2×2.5 |
36 37 38.5 |
6.3 6.6 10.5 21 |
YNyn0d11 | 0.53 |
HV-MV: 17.5-18.5 HV-LV: 10.5 MV-LV: 6.5 |
HV-MV: 10.5 HV-LV: 17.5-19 MV-LV: 6.5 |
4.9 | 40 |
| 8000 | 0.5 | 5.8 | 48 | |||||||
| 10000 | 0.47 | 6.9 | 56 | |||||||
| 12500 | 0.45 | 8.1 | 67 | |||||||
| 16000 | 0.42 | 9.8 | 81 | |||||||
| 20000 | 0.42 | 11.6 | 95 | |||||||
| 25000 | 0.38 | 13.5 | 113 | |||||||
| 31500 | 0.38 | 16.2 | 134 | |||||||
| 40000 | 0.35 | 19.1 | 161 | |||||||
| 50000 | 0.35 | 22.9 | 192 | |||||||
| 63000 | 0.32 | 27.1 | 230 | |||||||
* Values are reference data; project guarantees are confirmed in the technical agreement.
110kV oil-immersed three-phase double-winding on-load voltage regulating power transformer
|
Rated capacity (kVA) |
Rated voltage and tapping range | Vector group |
No load current (%) |
Impedance voltage (%) |
No load losses (kW) |
On load losses (kW) |
||
|---|---|---|---|---|---|---|---|---|
| HV |
Tapping range (%) |
LV | ||||||
| 6300 | 110 |
±4×1.25 ±6×1.25 ±8×1.25 |
6.3 6.6 10.5 21 |
YNd11 | 0.51 | 10.5 | 4.4 | 32 |
| 8000 | 0.51 | 5.3 | 38 | |||||
| 10000 | 0.47 | 6.2 | 45 | |||||
| 12500 | 0.47 | 7.4 | 53 | |||||
| 16000 | 0.44 | 8.9 | 66 | |||||
| 20000 | 0.44 | 10.6 | 79 | |||||
| 25000 | 0.41 | 12.5 | 94 | |||||
| 31500 | 0.41 | 14.9 | 111 | |||||
| 40000 | 0.37 | 10.5-18 | 17.8 | 140 | ||||
| 50000 | 0.37 | 21.0 | 175 | |||||
| 63000 | 0.34 | 25.0 | 209 | |||||
* Values are reference data; project guarantees are confirmed in the technical agreement.
110kV oil-immersed three-phase three-winding on-load voltage regulating power transformer
|
Rated capacity (kVA) |
Rated voltage and tapping range | Vector group |
No load current (%) |
Impedance voltage (%) |
No load losses (kW) |
On load losses (kW) |
|||
|---|---|---|---|---|---|---|---|---|---|
| HV |
Tapping range (%) |
MV | LV | ||||||
| 6300 | 110 |
±4×2.5 ±6×2.5 ±8×2.5 |
36 37 38.5 |
6.3 6.6 10.5 21 |
YNyn0d11 | 0.61 |
HV-MV: 10.5 HV-LV: 17.5-19 MV-LV: 6.5 |
5.3 | 40 |
| 8000 | 0.61 | 6.3 | 48 | ||||||
| 10000 | 0.57 | 7.5 | 56 | ||||||
| 12500 | 0.57 | 8.9 | 67 | ||||||
| 16000 | 0.54 | 10.6 | 81 | ||||||
| 20000 | 0.54 | 12.5 | 95 | ||||||
| 25000 | 0.5 | 14.9 | 113 | ||||||
| 31500 | 0.5 | 17.7 | 134 | ||||||
| 40000 | 0.46 | 21.2 | 161 | ||||||
| 50000 | 0.46 | 25.0 | 192 | ||||||
| 63000 | 0.42 | 29.8 | 230 | ||||||
* Values are reference data; project guarantees are confirmed in the technical agreement.
Packing & Delivering
Multi-layer protection and expert logistics for safe global transit.
FAQ's
Q: How Are Price And Lead Time Confirmed?
A: They are confirmed after reviewing the specification and quantity.
Q: What Information Is Needed For A Quotation? (Oil-Immersed Distribution Transformer)
A: Capacity; primary/secondary voltage; frequency; loss requirements; taps; site.
Q: Can Voltage Level Alone Determine A Model?
A: No. Capacity, winding arrangement, impedance, taps and site conditions are also required.