66 kV Oil-Immersed Power Transformer

66 kV Oil-Immersed Power Transformer
66 kV Oil-Immersed Power Transformer

Overview

A 66 kV oil-immersed power transformer is selected for power conversion at the specified system voltage level. The reference catalogue provides configurations with rated capacity, winding voltages, tapping ranges, vector groups and impedance values. On-load and off-circuit tap-changing arrangements are listed separately and must be selected to suit the operating requirement. The design review should establish the required number of windings, network voltages, load profile and installation environment. Rated voltage alone is not enough to define a complete transformer specification. Buyers should also provide the frequency, required losses, insulation requirements, cooling arrangement and applicable project specification. Accessories, terminal arrangements and protection interfaces are agreed with the installation designer. For replacement projects, include the existing nameplate and foundation drawing. The catalogue tables supplied with this material package are reference data from the existing product documents. Final guaranteed values, test scope and overall dimensions must be confirmed in the project technical agreement and approved drawing before manufacture.

Request a Quote

Features and Benefits

  • Separate tap-changing configurations support different operating requirements.
  • Project-specific electrical and mechanical review supports installation coordination.

Technical Specifications

66kV oil-immersed three-phase double-winding off-circuit tap changing power transformer

Rated capacity
(kVA)
Rated voltage and tapping range
Vector group
No load current
(%)
Impedance voltage
(%)
No load losses
(kW)
On load losses
(kW)
HV Tapping range
(%)
LV
3150 63
66
69
±5 6.3
6.6
10.5
YNd11 0.70 8 2.2 20.7
4000 0.64 2.6 24.6
5000 0.54 3.1 27.6
6300 ±2×2.5 0.48 9 4.0 30.8
8000 0.48 4.9 36.5
10000 0.45 5.8 43.0
12500 0.45 6.8 51.1
16000 0.42 8.3 62.8
20000 0.42 9.7 76.1
25000 0.38 11.4 90.0
31500 0.35 13.5 108.0
40000 0.35 16.2 126.9
50000 0.32 19.4 150.3
63000 0.29 22.9 178.2

* Values are reference data; project guarantees are confirmed in the technical agreement.


66kV oil-immersed three-phase double-winding on-load voltage regulating power transformer

Rated capacity
(kVA)
Rated voltage and tapping range Vector group No load current
(%)
Impedance voltage
(%)
No load losses
(kW)
On load losses
(kW)
HV Tapping range
(%)
LV
6300 63
66
69
±4×1.25
±6×1.25
±8×1.25
6.3
6.6
10.5
YNd11 0.48 9 4.4 30.8
8000 0.48 5.3 36.5
10000 0.45 6.2 43.0
12500 0.45 7.4 51.1
16000 0.42 8.9 62.8
20000 0.42 10.6 76.1
25000 0.38 12.5 90.0
31500 0.35 14.8 108.0
40000 0.35 17.7 126.9
50000 0.32 10~12 20.9 150.3
63000 0.29 24.7 178.2

* Values are reference data; project guarantees are confirmed in the technical agreement.

Outline Installation Dimensions

Packing & Delivering

Multi-layer protection and expert logistics for safe global transit.

Vacuum Packing
Vacuum Foil Packaging
Wooden Case
Solid Wood Export Cases
Global Routes
Worldwide Delivery

FAQ's

Q: How Are Price And Lead Time Confirmed?

A: They are confirmed after reviewing the specification and quantity.

Q: What Information Is Needed For A Quotation? (Oil-Immersed Distribution Transformer)

A: Capacity; primary/secondary voltage; frequency; loss requirements; taps; site.

Q: Can Voltage Level Alone Determine A Model?

A: No. Capacity, winding arrangement, impedance, taps and site conditions are also required.