The magnetic voltage regulator is a voltage regulation device that organically combines a saturable reactor with a transformer. The reactor is mainly responsible for regulating the input voltage of the transformer, while the transformer steps the adjustable input voltage up or down to any voltage value required by the load. The two are connected both electrically and magnetically. Structurally, it resembles an ordinary power transformer, but unlike other types of voltage regulators, it has no mechanical transmission device and no movable contacts. This contactless, moving-part-free characteristic makes it particularly suitable for high-voltage output or low-voltage, high-current output applications. At present, this type of regulator has been widely adopted as the voltage-regulating power supply for salt bath furnaces, electron bombardment furnaces, high-voltage electrostatic precipitators, and similar equipment.
Basic Structure and Circuit Relationship
A magnetic voltage regulator consists of two parts: a reactor and a transformer. The reactor is provided with an AC working winding and a DC control winding, while the transformer has a primary winding B1 and a secondary winding B2. The AC working winding G of the reactor is connected in series with the primary winding B1 of the transformer, and it is precisely this series connection that establishes the electrical link between the reactor and the transformer.
Working Principle
The voltage regulation process of a magnetic voltage regulator is essentially based on using a DC control current to change the magnetization state of the reactor core, thereby changing its effective AC permeability and impedance, and ultimately achieving continuous regulation of the load voltage.
When the input terminal of the magnetic voltage regulator is connected to a voltage U1 and the output terminal is connected to a rated load resistance R, if the DC control current Ik = 0, the reactor core is not magnetized by DC. At this point, the effective AC permeability is high, and the impedance reflected in winding G is much greater than the total primary impedance of the transformer. Consequently, the supply voltage U1 is essentially distributed across winding G, while the voltage on the primary side of the transformer, UB1, is very small; the load voltage is at its lower limit U2min.
As the DC control current Ik is gradually increased, the reactor core becomes magnetized by DC to varying degrees, and the effective AC permeability decreases accordingly. The voltage across winding G and the load voltage U2 then gradually increase. When Ik reaches its rated value Ika, the reactor core becomes highly magnetized and saturated by the DC, the effective AC permeability reaches its minimum, and the reactor impedance becomes minimal compared with the total primary impedance of the transformer. At this point, the supply voltage U1 is essentially distributed across winding B1, and the load voltage U2 reaches its maximum value U2max.
It can thus be seen that by continuously adjusting the magnitude of the DC control current Ik, smooth stepless regulation of the load voltage U2 from the lower limit to the maximum value is achieved. The entire process involves no mechanical movement and no contact switching, and the response is smooth—this is the key advantage that distinguishes the magnetic voltage regulator from traditional voltage regulation methods.